Catalog · Copeland

Copeland CR42K6E-TF5 (R407C hermetic recip, 50 Hz, AC)

Compressor — R407C compressor — 8.9 kW cooling, 3.15 kW input, COP 2.83 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland CR42K6E-TF5 (R407C hermetic recip, 50 Hz, AC)
RefrigerantR407C
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C8.94 kW
Input power @ 7.2/54.4 °C3.15 kW
COP @ 7.2/54.4 °C2.83

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 303.011.472.04
-20 / 402.321.481.57
-10 / 306.111.863.29
-10 / 404.892.002.44
0 / 3010.992.145.14
0 / 409.142.453.73
0 / 605.562.732.04
10 / 3017.452.207.95
10 / 4014.902.735.47
10 / 6010.043.462.90

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland CR42K6E-PFV (R22 hermetic recip, 60 Hz, AC)R22
compressorsCopeland CR42K6E-TFD (R407C hermetic recip, 60 Hz, AC)R407C

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy