Catalog · Copeland

Copeland CS13K6E-PFZ (R404A hermetic recip, 50 Hz, EM)

Compressor — R404A compressor — 4.3 kW cooling, 2.27 kW input, COP 1.88 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland CS13K6E-PFZ (R404A hermetic recip, 50 Hz, EM)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool34.7 / 0.0 K
Cooling capacity @ 7.2/54.4 °C4.26 kW
Input power @ 7.2/54.4 °C2.27 kW
COP @ 7.2/54.4 °C1.88

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 34.7 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 301.350.961.41
-30 / 400.940.911.03
-20 / 302.701.292.09
-20 / 402.001.301.54
-20 / 600.841.150.73
-10 / 304.671.592.95
-10 / 403.651.702.15
-10 / 601.771.721.03
0 / 307.041.684.20
0 / 405.631.932.92
0 / 602.942.221.33

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland CS13K6E-TF5 (R404A hermetic recip, 60 Hz, EM)R404A
compressorsCopeland CS13K6E-TF5 (R407A hermetic recip, 60 Hz, MT)R407A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy