Catalog · Copeland

Copeland CS16K6E-TF5 (R404A hermetic recip, 60 Hz, EM)

Compressor — R404A compressor — 5.9 kW cooling, 3.22 kW input, COP 1.83 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland CS16K6E-TF5 (R404A hermetic recip, 60 Hz, EM)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool34.7 / 0.0 K
Cooling capacity @ 7.2/54.4 °C5.87 kW
Input power @ 7.2/54.4 °C3.22 kW
COP @ 7.2/54.4 °C1.83

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 34.7 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 301.881.241.52
-30 / 401.331.171.13
-20 / 303.741.722.17
-20 / 402.771.711.63
-20 / 601.251.550.80
-10 / 306.492.163.00
-10 / 405.082.282.23
-10 / 602.542.321.09
0 / 309.642.344.12
0 / 407.782.662.92
0 / 604.173.061.36

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland CS16K6E-PFZ (R404A hermetic recip, 50 Hz, EM)R404A
compressorsCopeland CS16K6E-PFV (R407A hermetic recip, 60 Hz, MT)R407A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy