Compressor — R404A compressor — 11.3 kW cooling, 5.46 kW input, COP 2.07 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland CS27KQME-TF5 (R404A hermetic recip, 60 Hz, MT) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 30.5 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 11.30 kW |
| Input power @ 7.2/54.4 °C | 5.46 kW |
| COP @ 7.2/54.4 °C | 2.07 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.5 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 6.30 | 2.75 | 2.29 |
| -20 / 40 | 4.96 | 2.87 | 1.73 |
| -10 / 30 | 10.57 | 3.41 | 3.10 |
| -10 / 40 | 8.43 | 3.68 | 2.29 |
| -10 / 60 | 4.17 | 3.78 | 1.10 |
| 0 / 30 | 16.38 | 3.92 | 4.18 |
| 0 / 40 | 13.30 | 4.39 | 3.03 |
| 0 / 60 | 7.16 | 4.93 | 1.45 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland CS27KQME-TF5 (R404A hermetic recip, 50 Hz, MT) | R404A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.