Compressor — R404A compressor — 11.7 kW cooling, 4.72 kW input, COP 2.48 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland CS47K7ME-TFD (R404A hermetic recip, 60 Hz, HT) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 11.71 kW |
| Input power @ 7.2/54.4 °C | 4.72 kW |
| COP @ 7.2/54.4 °C | 2.48 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 11.64 | 2.65 | 4.40 |
| -10 / 40 | 8.67 | 3.06 | 2.83 |
| -10 / 60 | 5.13 | 3.83 | 1.34 |
| 0 / 30 | 17.93 | 3.24 | 5.54 |
| 0 / 40 | 14.27 | 3.72 | 3.84 |
| 0 / 60 | 9.63 | 4.70 | 2.05 |
| 10 / 30 | 23.67 | 3.47 | 6.81 |
| 10 / 40 | 19.39 | 3.98 | 4.87 |
| 10 / 60 | 13.79 | 5.06 | 2.72 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.