Compressor — R404A compressor — 15.6 kW cooling, 6.80 kW input, COP 2.29 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland CS62K7ME-TFD (R404A hermetic recip, 60 Hz, HT) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 15.58 kW |
| Input power @ 7.2/54.4 °C | 6.80 kW |
| COP @ 7.2/54.4 °C | 2.29 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 15.24 | 3.81 | 4.01 |
| -10 / 40 | 11.65 | 4.41 | 2.64 |
| -10 / 60 | 6.37 | 5.48 | 1.16 |
| 0 / 30 | 23.26 | 4.65 | 5.00 |
| 0 / 40 | 18.87 | 5.36 | 3.52 |
| 0 / 60 | 12.09 | 6.71 | 1.80 |
| 10 / 30 | 31.34 | 5.02 | 6.24 |
| 10 / 40 | 26.25 | 5.77 | 4.55 |
| 10 / 60 | 18.15 | 7.27 | 2.50 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.