Compressor — R450A compressor with a 10-coefficient AHRI 540 map.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland RRT73C1E-CAB (R450A hermetic recip, 50 Hz, HT) |
| Refrigerant | R450A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 23.6 / 0.0 K |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 23.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -23 to 13 °C, condensing 21 to 60 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 0.73 | 0.39 | 1.88 |
| -20 / 40 | 0.59 | 0.40 | 1.47 |
| -20 / 60 | 0.40 | 0.40 | 1.00 |
| -10 / 30 | 1.17 | 0.47 | 2.46 |
| -10 / 40 | 1.00 | 0.50 | 1.98 |
| -10 / 60 | 0.70 | 0.55 | 1.27 |
| 0 / 30 | 1.74 | 0.56 | 3.12 |
| 0 / 40 | 1.53 | 0.60 | 2.55 |
| 0 / 60 | 1.10 | 0.69 | 1.60 |
| 10 / 30 | 2.50 | 0.65 | 3.82 |
| 10 / 40 | 2.23 | 0.70 | 3.18 |
| 10 / 60 | 1.64 | 0.82 | 2.01 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland RRT73C1E-CAV (R134A hermetic recip, 60 Hz, HT) | R134a |
| compressors | Copeland RRT73C1E-CAA (R450A hermetic recip, 60 Hz, HT) | R450A |
| compressors | Copeland RRT73C1E-CAB (R513A hermetic recip, 50 Hz, HT) | R513A |
| compressors | Copeland RRT73C1E-CAV (R513A hermetic recip, 60 Hz, HT) | R513A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.