Copeland RST55C1E-CFA (R407C hermetic recip, 60 Hz, HT)

Compressor — R407C compressor — 2.5 kW cooling, 1.11 kW input, COP 2.21 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland RST55C1E-CFA (R407C hermetic recip, 60 Hz, HT)
RefrigerantR407C
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool20.8 / 0.0 K
Cooling capacity @ 7.2/54.4 °C2.45 kW
Input power @ 7.2/54.4 °C1.11 kW
COP @ 7.2/54.4 °C2.21

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 20.8 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 301.730.662.62
-10 / 401.500.732.05
0 / 302.710.753.62
0 / 402.370.842.81
0 / 601.621.041.56
10 / 304.080.874.71
10 / 403.570.973.66
10 / 602.491.251.99

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland RST55C1E-CAV (R404A hermetic recip, 60 Hz, EM)R404A
compressorsCopeland RST55C1E-CAV (R448A hermetic recip, 60 Hz, MT)R448A
compressorsCopeland RST55C1E-CAV (R449A hermetic recip, 60 Hz, MT)R449A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy