Compressor — R454B compressor — 43.0 kW cooling, 13.26 kW input, COP 3.24 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland YAD147K1E-TE5 (R454B scroll, 60 Hz, AC) |
| Refrigerant | R454B |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 42.99 kW |
| Input power @ 7.2/54.4 °C | 13.26 kW |
| COP @ 7.2/54.4 °C | 3.24 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 10-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 22.52 | 5.83 | 3.86 |
| -20 / 30 | 19.85 | 7.49 | 2.65 |
| -10 / 10 | 34.87 | 5.63 | 6.19 |
| -10 / 30 | 30.09 | 7.67 | 3.92 |
| 0 / 30 | 43.59 | 7.93 | 5.50 |
| 20 / 60 | 61.07 | 15.16 | 4.03 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.