Catalog · Copeland

Copeland YAU171K1E-TFD (R454B scroll, 50 Hz, AC)

Compressor — R454B compressor — 51.1 kW cooling, 15.52 kW input, COP 3.29 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YAU171K1E-TFD (R454B scroll, 50 Hz, AC)
RefrigerantR454B
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C51.09 kW
Input power @ 7.2/54.4 °C15.52 kW
COP @ 7.2/54.4 °C3.29

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -23 to 25 °C, condensing 10 to 66 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1025.926.214.18
-20 / 3022.538.772.57
-20 / 6014.7318.460.80
-10 / 1040.265.587.22
-10 / 3034.919.043.86
-10 / 6024.5018.101.35
0 / 1058.994.1314.30
0 / 3050.858.855.75
0 / 6036.5717.852.05
20 / 3098.306.7614.54
20 / 6072.5517.314.19

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YAU171K1E-TFD (R454B scroll, 60 Hz, AC)R454B

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy