Catalog · Copeland

Copeland YAU195K1E-TFD (R454B scroll, 50 Hz, AC)

Compressor — R454B compressor — 48.5 kW cooling, 14.51 kW input, COP 3.34 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YAU195K1E-TFD (R454B scroll, 50 Hz, AC)
RefrigerantR454B
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C48.47 kW
Input power @ 7.2/54.4 °C14.51 kW
COP @ 7.2/54.4 °C3.34

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -23 to 25 °C, condensing 10 to 66 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1024.955.674.40
-20 / 3021.518.162.64
-20 / 6014.4817.090.85
-10 / 1038.715.157.52
-10 / 3033.368.393.97
-10 / 6023.2116.901.37
0 / 1056.583.9514.34
0 / 3048.698.225.93
0 / 6034.5016.722.06
20 / 3094.086.4414.61
20 / 6069.0416.174.27

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YAU195K1E-TFD (R454B scroll, 60 Hz, AC)R454B

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy