Catalog · Copeland

Copeland YAU213K1E-TFD (R454B scroll, 50 Hz, AC)

Compressor — R454B compressor — 51.8 kW cooling, 15.92 kW input, COP 3.25 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YAU213K1E-TFD (R454B scroll, 50 Hz, AC)
RefrigerantR454B
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C51.75 kW
Input power @ 7.2/54.4 °C15.92 kW
COP @ 7.2/54.4 °C3.25

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -23 to 25 °C, condensing 10 to 66 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1028.295.535.12
-20 / 3023.428.962.61
-20 / 6016.3118.140.90
-10 / 1042.495.278.07
-10 / 3035.899.033.98
-10 / 6024.8618.191.37
0 / 1061.334.5313.55
0 / 3052.448.805.96
0 / 6036.6618.242.01
20 / 30101.356.8914.71
20 / 6073.5617.744.15

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YAU213K1E-TFE (R454B scroll, 60 Hz, AC)R454B

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy