Catalog · Copeland

Copeland YB12K1E-TFD (R448A scroll, 60 Hz, MT)

Compressor — R448A compressor with a 10-coefficient AHRI 540 map.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YB12K1E-TFD (R448A scroll, 60 Hz, MT)
RefrigerantR448A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool26.4 / 0.0 K

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 103.750.854.39
-20 / 303.111.262.46
-10 / 105.690.916.22
-10 / 304.741.383.43
-10 / 603.172.341.35
0 / 306.971.494.66
0 / 604.632.551.82

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YB12K1E-TFD (R1234yf scroll, 60 Hz, MT)R1234yf
compressorsCopeland YB12K1E-TFD (R134A scroll, 60 Hz, MT)R134a
compressorsCopeland YB12K1E-TFD (R404A scroll, 60 Hz, MT)R404A
compressorsCopeland YB12K1E-TFD (R407A scroll, 60 Hz, MT)R407A
compressorsCopeland YB12K1E-PFJ (R407C scroll, 50 Hz, MT)R407C
compressorsCopeland YB12K1E-TFD (R407C scroll, 60 Hz, MT)R407C
compressorsCopeland YB12K1E-TFD (R407F scroll, 60 Hz, MT)R407F
compressorsCopeland YB12K1E-TFD (R448A scroll, 50 Hz, MT)R448A
compressorsCopeland YB12K1E-TFD (R449A scroll, 60 Hz, MT)R449A
compressorsCopeland YB12K1E-TFD (R450A scroll, 60 Hz, MT)R450A
compressorsCopeland YB12K1E-TFD (R454A scroll, 60 Hz, MT)R454A
compressorsCopeland YB12K1E-PFJ (R454C scroll, 50 Hz, MT)R454C

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy