Compressor — R454A compressor — 15.8 kW cooling, 5.92 kW input, COP 2.67 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland YB38KAE-PFJ (R454A scroll, 50 Hz, MT) |
| Refrigerant | R454A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 26.4 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 15.81 kW |
| Input power @ 7.2/54.4 °C | 5.92 kW |
| COP @ 7.2/54.4 °C | 2.67 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 9.07 | 2.24 | 4.06 |
| -20 / 30 | 7.57 | 3.28 | 2.31 |
| -10 / 10 | 13.61 | 2.34 | 5.81 |
| -10 / 30 | 11.39 | 3.50 | 3.25 |
| -10 / 60 | 7.65 | 6.40 | 1.19 |
| 0 / 30 | 16.66 | 3.61 | 4.62 |
| 0 / 60 | 11.12 | 6.57 | 1.69 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland YB38KAE-PFV (R454A scroll, 60 Hz, MT) | R454A |
| compressors | Copeland YB38KAE-PFJ (R454C scroll, 50 Hz, MT) | R454C |
| compressors | Copeland YB38KAE-PFV (R454C scroll, 60 Hz, MT) | R454C |
| compressors | Copeland YB38KAE-PFJ (R455A scroll, 50 Hz, MT) | R455A |
| compressors | Copeland YB38KAE-PFV (R455A scroll, 60 Hz, MT) | R455A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.