Catalog · Copeland

Copeland YBD28KAE-TF5 (R454C scroll, 50 Hz, MT)

Compressor — R454C compressor with a 10-coefficient AHRI 540 map.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YBD28KAE-TF5 (R454C scroll, 50 Hz, MT)
RefrigerantR454C
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool26.4 / 0.0 K

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 105.611.304.32
-20 / 304.711.972.39
-10 / 108.421.326.39
-10 / 307.102.113.36
-10 / 604.773.731.28
0 / 3010.392.144.85
0 / 606.983.851.81

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YBD28KAE-TF7 (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland YBD28KAE-TF7 (R404A scroll, 60 Hz, MT)R404A
compressorsCopeland YBD28KAE-TF7 (R407A scroll, 60 Hz, MT)R407A
compressorsCopeland YBD28KAE-TF7 (R407C scroll, 60 Hz, MT)R407C
compressorsCopeland YBD28KAE-TF7 (R407F scroll, 60 Hz, MT)R407F
compressorsCopeland YBD28KAE-TF7 (R448A scroll, 60 Hz, MT)R448A
compressorsCopeland YBD28KAE-TF7 (R449A scroll, 60 Hz, MT)R449A
compressorsCopeland YBD28KAE-TF5 (R454A scroll, 50 Hz, MT)R454A
compressorsCopeland YBD28KAE-TF5 (R454A scroll, 60 Hz, MT)R454A
compressorsCopeland YBD28KAE-TF5 (R454C scroll, 60 Hz, MT)R454C
compressorsCopeland YBD28KAE-TF5 (R455A scroll, 50 Hz, MT)R455A
compressorsCopeland YBD28KAE-TF5 (R455A scroll, 60 Hz, MT)R455A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy