Catalog · Copeland

Copeland YBD68KAE-TFD (R452A scroll, 50 Hz, MT)

Compressor — R452A compressor — 27.2 kW cooling, 10.36 kW input, COP 2.62 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YBD68KAE-TFD (R452A scroll, 50 Hz, MT)
RefrigerantR452A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool26.4 / 0.0 K
Cooling capacity @ 7.2/54.4 °C27.18 kW
Input power @ 7.2/54.4 °C10.36 kW
COP @ 7.2/54.4 °C2.62

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 3014.205.562.55
-20 / 4012.546.771.85
-10 / 3021.146.023.51
-10 / 4018.647.272.56
-10 / 6013.1311.041.19
0 / 3030.556.284.86
0 / 4026.877.643.52
0 / 6018.8411.381.66

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YBD68KAE-TFD (R452A scroll, 60 Hz, MT)R452A
compressorsCopeland YBD68KAE-TFD (R513A scroll, 50 Hz, HT)R513A
compressorsCopeland YBD68KAE-TFD (R513A scroll, 60 Hz, HT)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy