Compressor — R455A compressor with a 10-coefficient AHRI 540 map.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland YF09KSE-TF5 (R455A scroll, 50 Hz, LL) |
| Refrigerant | R455A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 34.7 / 0.0 K |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 34.7 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 7-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / -0 | 2.27 | 0.81 | 2.81 |
| -40 / 30 | 1.75 | 1.39 | 1.26 |
| -30 / -0 | 3.57 | 0.88 | 4.04 |
| -30 / 30 | 2.84 | 1.55 | 1.83 |
| -20 / 30 | 4.39 | 1.73 | 2.54 |
| 0 / 30 | 9.53 | 2.09 | 4.56 |
| 0 / 60 | 6.53 | 3.45 | 1.89 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland YF09KSE-PFV (R404A scroll, 50 Hz, LL) | R404A |
| compressors | Copeland YF09KSE-PFV (R407A scroll, 50 Hz, LL) | R407A |
| compressors | Copeland YF09KSE-PFV (R407F scroll, 50 Hz, LL) | R407F |
| compressors | Copeland YF09KSE-PFV (R448A scroll, 50 Hz, LL) | R448A |
| compressors | Copeland YF09KSE-PFV (R449A scroll, 50 Hz, LL) | R449A |
| compressors | Copeland YF09KSE-TF5 (R454A scroll, 50 Hz, LL) | R454A |
| compressors | Copeland YF09KSE-TF5 (R454A scroll, 60 Hz, LL) | R454A |
| compressors | Copeland YF09KSE-TF5 (R454C scroll, 50 Hz, LL) | R454C |
| compressors | Copeland YF09KSE-TF5 (R454C scroll, 60 Hz, LL) | R454C |
| compressors | Copeland YF09KSE-TF5 (R455A scroll, 60 Hz, LL) | R455A |
| compressors | Copeland YF09KSE-PFV (R507 scroll, 50 Hz, LL) | R507 |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.