Catalog · Copeland

Copeland YF22KAE-TFC (R454A scroll, 60 Hz, LL)

Compressor — R454A compressor — 29.7 kW cooling, 11.10 kW input, COP 2.68 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YF22KAE-TFC (R454A scroll, 60 Hz, LL)
RefrigerantR454A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool44.4 / 0.0 K
Cooling capacity @ 7.2/54.4 °C29.75 kW
Input power @ 7.2/54.4 °C11.10 kW
COP @ 7.2/54.4 °C2.68

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 44.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 106.903.432.01
-40 / 305.804.601.26
-30 / 1010.993.842.86
-30 / 309.355.241.78
-20 / 1017.004.303.96
-20 / 3014.415.932.43

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YF22KAE-TFC (R454A scroll, 50 Hz, LL)R454A
compressorsCopeland YF22KAE-TFC (R454C scroll, 50 Hz, LL)R454C
compressorsCopeland YF22KAE-TFC (R454C scroll, 60 Hz, LL)R454C
compressorsCopeland YF22KAE-TFC (R455A scroll, 50 Hz, LL)R455A
compressorsCopeland YF22KAE-TFC (R455A scroll, 60 Hz, LL)R455A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy