Copeland YF26KAE-TFD (R454A scroll, 50 Hz, LL)

Compressor — R454A compressor — 28.6 kW cooling, 10.83 kW input, COP 2.64 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YF26KAE-TFD (R454A scroll, 50 Hz, LL)
RefrigerantR454A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool47.2 / 0.0 K
Cooling capacity @ 7.2/54.4 °C28.65 kW
Input power @ 7.2/54.4 °C10.83 kW
COP @ 7.2/54.4 °C2.64

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 106.623.212.06
-40 / 305.574.301.29
-30 / 1010.603.742.84
-30 / 308.974.951.81
-20 / 1016.414.283.83
-20 / 3013.855.702.43

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YF26KAE-TFD (R449A scroll, 50 Hz, ML)R449A
compressorsCopeland YF26KAE-TFD (R452A scroll, 60 Hz, LL)R452A
compressorsCopeland YF26KAE-TFD (R454A scroll, 60 Hz, LL)R454A
compressorsCopeland YF26KAE-TFD (R454C scroll, 50 Hz, ML)R454C
compressorsCopeland YF26KAE-TFD (R454C scroll, 60 Hz, LL)R454C
compressorsCopeland YF26KAE-TFD (R455A scroll, 50 Hz, LL)R455A
compressorsCopeland YF26KAE-TFD (R455A scroll, 60 Hz, LL)R455A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy