Copeland YH06K1E-PFJ (R407C scroll, 50 Hz, HP)

Compressor — R407C compressor — 5.2 kW cooling, 1.82 kW input, COP 2.88 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YH06K1E-PFJ (R407C scroll, 50 Hz, HP)
RefrigerantR407C
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 2.8 K
Cooling capacity @ 7.2/54.4 °C5.22 kW
Input power @ 7.2/54.4 °C1.82 kW
COP @ 7.2/54.4 °C2.88

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 2.8 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -25 to 10 °C, condensing 21 to 65 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 302.191.032.13
-20 / 401.951.231.58
-20 / 601.421.860.76
-10 / 303.531.093.23
-10 / 403.171.302.45
-10 / 602.381.951.22
0 / 305.391.174.63
0 / 404.871.353.59
0 / 603.722.001.86
10 / 307.901.276.24
10 / 407.161.435.01
10 / 605.572.052.72

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YH06K1E-TFD (R1234yf scroll, 60 Hz, HP)R1234yf
compressorsCopeland YH06K1E-TFD (R134A scroll, 60 Hz, HP)R134a
compressorsCopeland YH06K1E-TFD (R407C scroll, 60 Hz, HP)R407C
compressorsCopeland YH06K1E-TFD (R454C scroll, 60 Hz, HP)R454C
compressorsCopeland YH06K1E-TFD (R513A scroll, 60 Hz, HP)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy