Catalog · Copeland

Copeland YH07K1E-PFJ (R407C scroll, 50 Hz, HP)

Compressor — R407C compressor — 9.1 kW cooling, 3.24 kW input, COP 2.80 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YH07K1E-PFJ (R407C scroll, 50 Hz, HP)
RefrigerantR407C
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 2.8 K
Cooling capacity @ 7.2/54.4 °C9.06 kW
Input power @ 7.2/54.4 °C3.24 kW
COP @ 7.2/54.4 °C2.80

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 2.8 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -25 to 10 °C, condensing 21 to 65 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 303.931.812.18
-20 / 403.542.121.67
-20 / 602.733.030.90
-10 / 306.191.903.26
-10 / 405.582.252.48
-10 / 604.203.281.28
0 / 309.442.004.72
0 / 408.522.373.60
0 / 606.413.491.84
10 / 3013.912.136.53
10 / 4012.592.505.04
10 / 609.593.692.60

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YH07K1E-TFD (R1234yf scroll, 60 Hz, HP)R1234yf
compressorsCopeland YH07K1E-TFD (R134A scroll, 60 Hz, HP)R134a
compressorsCopeland YH07K1E-TFD (R407C scroll, 60 Hz, HP)R407C
compressorsCopeland YH07K1E-PFJ (R454C scroll, 50 Hz, HP)R454C
compressorsCopeland YH07K1E-TFD (R454C scroll, 60 Hz, HP)R454C
compressorsCopeland YH07K1E-TFD (R513A scroll, 60 Hz, HP)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy