Compressor — R454C compressor with a 10-coefficient AHRI 540 map.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland YH09K1E-TFD (R454C scroll, 60 Hz, HP) |
| Refrigerant | R454C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 2.8 K |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 2.8 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -25 to 10 °C, condensing 21 to 65 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 5.34 | 2.22 | 2.41 |
| -20 / 40 | 4.75 | 2.65 | 1.79 |
| -20 / 60 | 3.42 | 3.72 | 0.92 |
| -10 / 30 | 8.26 | 2.37 | 3.49 |
| -10 / 40 | 7.36 | 2.80 | 2.62 |
| -10 / 60 | 5.35 | 4.01 | 1.33 |
| 0 / 30 | 12.38 | 2.49 | 4.96 |
| 0 / 40 | 11.05 | 2.93 | 3.77 |
| 0 / 60 | 8.11 | 4.29 | 1.89 |
| 10 / 30 | 18.00 | 2.59 | 6.95 |
| 10 / 40 | 16.11 | 3.04 | 5.30 |
| 10 / 60 | 12.00 | 4.54 | 2.64 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland YH09K1E-TFD (R1234yf scroll, 60 Hz, HP) | R1234yf |
| compressors | Copeland YH09K1E-TFD (R134A scroll, 60 Hz, HP) | R134a |
| compressors | Copeland YH09K1E-PFJ (R407C scroll, 50 Hz, HP) | R407C |
| compressors | Copeland YH09K1E-TFD (R407C scroll, 60 Hz, HP) | R407C |
| compressors | Copeland YH09K1E-PFJ (R454C scroll, 50 Hz, HP) | R454C |
| compressors | Copeland YH09K1E-TFD (R513A scroll, 60 Hz, HP) | R513A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.