Catalog · Copeland

Copeland YS14KAE-PFJ (R407A scroll, 50 Hz, EM)

Compressor — R407A compressor — 5.8 kW cooling, 2.05 kW input, COP 2.84 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YS14KAE-PFJ (R407A scroll, 50 Hz, EM)
RefrigerantR407A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.6 / 0.0 K
Cooling capacity @ 7.2/54.4 °C5.82 kW
Input power @ 7.2/54.4 °C2.05 kW
COP @ 7.2/54.4 °C2.84

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 101.980.742.69
-30 / 301.651.001.65
-20 / 103.150.784.05
-20 / 302.661.132.35
-10 / 104.840.796.13
-10 / 304.091.233.33
-10 / 602.772.251.23
0 / 306.061.254.85
0 / 604.072.321.75

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YS14KAE-TF5 (R134A scroll, 50 Hz, HT)R134a
compressorsCopeland YS14KAE-TF5 (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland YS14KAE-PFJ (R22 scroll, 50 Hz, HT)R22
compressorsCopeland YS14KAE-PFV (R22 scroll, 60 Hz, HT)R22
compressorsCopeland YS14KAE-PFJ (R404A scroll, 50 Hz, EM)R404A
compressorsCopeland YS14KAE-TF5 (R407C scroll, 50 Hz, HT)R407C
compressorsCopeland YS14KAE-TF5 (R407C scroll, 60 Hz, HT)R407C
compressorsCopeland YS14KAE-PFJ (R448A scroll, 50 Hz, EM)R448A
compressorsCopeland YS14KAE-PFJ (R449A scroll, 50 Hz, EM)R449A
compressorsCopeland YS14KAE-PFJ (R507 scroll, 50 Hz, EM)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy