Catalog · Copeland

Copeland YS21KAE-PFJ (R404A scroll, 50 Hz, EM)

Compressor — R404A compressor — 8.0 kW cooling, 3.40 kW input, COP 2.37 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YS21KAE-PFJ (R404A scroll, 50 Hz, EM)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.6 / 0.0 K
Cooling capacity @ 7.2/54.4 °C8.04 kW
Input power @ 7.2/54.4 °C3.40 kW
COP @ 7.2/54.4 °C2.37

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 103.931.173.37
-30 / 303.141.711.83
-20 / 105.961.324.52
-20 / 304.811.952.46
-20 / 602.823.150.90
-10 / 108.861.396.39
-10 / 307.122.093.40
-10 / 604.223.511.20
0 / 3010.222.134.79
0 / 606.053.741.62

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YS21KAE-TF5 (R134A scroll, 50 Hz, HT)R134a
compressorsCopeland YS21KAE-TF5 (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland YS21KAE-PFJ (R22 scroll, 50 Hz, HT)R22
compressorsCopeland YS21KAE-PFV (R22 scroll, 60 Hz, HT)R22
compressorsCopeland YS21KAE-PFJ (R404A scroll, 60 Hz, EM)R404A
compressorsCopeland YS21KAE-PFJ (R407A scroll, 50 Hz, EM)R407A
compressorsCopeland YS21KAE-PFJ (R407A scroll, 60 Hz, EM)R407A
compressorsCopeland YS21KAE-TF5 (R407C scroll, 50 Hz, HT)R407C
compressorsCopeland YS21KAE-TF5 (R407C scroll, 60 Hz, HT)R407C
compressorsCopeland YS21KAE-PFJ (R448A scroll, 50 Hz, EM)R448A
compressorsCopeland YS21KAE-PFJ (R448A scroll, 60 Hz, EM)R448A
compressorsCopeland YS21KAE-PFJ (R449A scroll, 50 Hz, EM)R449A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy