Catalog · Copeland

Copeland YS23KSE-TF5 (R454A scroll, 50 Hz, EM)

Compressor — R454A compressor — 9.9 kW cooling, 3.60 kW input, COP 2.74 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YS23KSE-TF5 (R454A scroll, 50 Hz, EM)
RefrigerantR454A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.6 / 0.0 K
Cooling capacity @ 7.2/54.4 °C9.86 kW
Input power @ 7.2/54.4 °C3.60 kW
COP @ 7.2/54.4 °C2.74

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 7-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 303.071.761.74
-30 / 402.762.101.32
-20 / 304.751.952.44
-20 / 404.282.321.84
-10 / 307.102.143.33
-10 / 406.402.532.52
-10 / 604.763.671.30
0 / 3010.292.304.48
0 / 409.282.713.43
0 / 606.943.881.79

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YS23KSE-PFV (R404A scroll, 50 Hz, EM)R404A
compressorsCopeland YS23KSE-TF5 (R454A scroll, 60 Hz, EM)R454A
compressorsCopeland YS23KSE-TF5 (R454C scroll, 50 Hz, EM)R454C
compressorsCopeland YS23KSE-TF5 (R454C scroll, 60 Hz, EM)R454C
compressorsCopeland YS23KSE-TF5 (R455A scroll, 50 Hz, EM)R455A
compressorsCopeland YS23KSE-TF5 (R455A scroll, 60 Hz, EM)R455A
compressorsCopeland YS23KSE-PFV (R507 scroll, 50 Hz, EM)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy