Compressor — R407C compressor — 14.3 kW cooling, 5.12 kW input, COP 2.80 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland YS30KAE-TF5 (R407C scroll, 60 Hz, HT) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 18.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 14.33 kW |
| Input power @ 7.2/54.4 °C | 5.12 kW |
| COP @ 7.2/54.4 °C | 2.80 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 18.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -12 to 13 °C, condensing 21 to 66 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 10.33 | 2.96 | 3.49 |
| -10 / 40 | 9.26 | 3.61 | 2.57 |
| -10 / 60 | 6.98 | 5.27 | 1.33 |
| 0 / 30 | 15.24 | 3.02 | 5.05 |
| 0 / 40 | 13.63 | 3.74 | 3.64 |
| 0 / 60 | 10.19 | 5.62 | 1.81 |
| 10 / 30 | 21.84 | 3.04 | 7.18 |
| 10 / 40 | 19.53 | 3.80 | 5.14 |
| 10 / 60 | 14.61 | 5.82 | 2.51 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland YS30KAE-TF5 (R134A scroll, 50 Hz, HT) | R134a |
| compressors | Copeland YS30KAE-TF5 (R134A scroll, 60 Hz, HT) | R134a |
| compressors | Copeland YS30KAE-PFJ (R404A scroll, 50 Hz, EM) | R404A |
| compressors | Copeland YS30KAE-PFJ (R404A scroll, 60 Hz, EM) | R404A |
| compressors | Copeland YS30KAE-PFJ (R407A scroll, 50 Hz, EM) | R407A |
| compressors | Copeland YS30KAE-PFJ (R407A scroll, 60 Hz, EM) | R407A |
| compressors | Copeland YS30KAE-TF5 (R407C scroll, 50 Hz, HT) | R407C |
| compressors | Copeland YS30KAE-PFJ (R448A scroll, 50 Hz, EM) | R448A |
| compressors | Copeland YS30KAE-PFJ (R448A scroll, 60 Hz, EM) | R448A |
| compressors | Copeland YS30KAE-PFJ (R449A scroll, 50 Hz, EM) | R449A |
| compressors | Copeland YS30KAE-PFJ (R449A scroll, 60 Hz, EM) | R449A |
| compressors | Copeland YS30KAE-PFJ (R507 scroll, 50 Hz, EM) | R507 |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.