Catalog · Copeland

Copeland ZB114K5E-TFD (R448A scroll, 60 Hz, MT)

Compressor — R448A compressor with a 10-coefficient AHRI 540 map.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZB114K5E-TFD (R448A scroll, 60 Hz, MT)
RefrigerantR448A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool25.0 / 0.0 K

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 25.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1027.956.694.18
-20 / 3022.0910.172.17
-10 / 1042.866.946.17
-10 / 3035.3210.333.42
-10 / 6019.6219.820.99
0 / 3052.5510.664.93
0 / 6033.7419.931.69
10 / 3075.4811.236.72
10 / 6050.8920.272.51

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZB114K5E-TFD (R134A scroll, 50 Hz, HT)R134a
compressorsCopeland ZB114K5E-TFD (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland ZB114K5E-TFD (R404A scroll, 50 Hz, MT)R404A
compressorsCopeland ZB114K5E-TFD (R404A scroll, 60 Hz, MT)R404A
compressorsCopeland ZB114K5E-TFD (R407A scroll, 60 Hz, MT)R407A
compressorsCopeland ZB114K5E-TFD (R407C scroll, 60 Hz, MT)R407C
compressorsCopeland ZB114K5E-TFD (R407F scroll, 60 Hz, MT)R407F
compressorsCopeland ZB114K5E-TFD (R448A scroll, 50 Hz, MT)R448A
compressorsCopeland ZB114K5E-TFD (R449A scroll, 60 Hz, MT)R449A
compressorsCopeland ZB114K5E-TFD (R507 scroll, 60 Hz, MT)R507
compressorsCopeland ZB114K5E-TFD (R513A scroll, 50 Hz, HT)R513A
compressorsCopeland ZB114K5E-TFD (R513A scroll, 60 Hz, HT)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy