Compressor — R404A compressor — 19.2 kW cooling, 7.55 kW input, COP 2.55 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZB58K5E-TFD (R404A scroll, 50 Hz, MT) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 26.4 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 19.22 kW |
| Input power @ 7.2/54.4 °C | 7.55 kW |
| COP @ 7.2/54.4 °C | 2.55 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 13.98 | 2.95 | 4.73 |
| -20 / 30 | 11.27 | 4.41 | 2.56 |
| -10 / 10 | 20.67 | 3.09 | 6.69 |
| -10 / 30 | 16.88 | 4.55 | 3.71 |
| -10 / 60 | 9.16 | 8.84 | 1.04 |
| 0 / 30 | 24.21 | 4.66 | 5.20 |
| 0 / 60 | 13.93 | 8.71 | 1.60 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZB58K5E-TFD (R134A scroll, 60 Hz, HT) | R134a |
| compressors | Copeland ZB58K5E-TFD (R507 scroll, 50 Hz, MT) | R507 |
| compressors | Copeland ZB58K5E-TFD (R513A scroll, 60 Hz, HT) | R513A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |