Catalog · Copeland

Copeland ZB66KCE-TF5 (R407A scroll, 60 Hz, MT)

Compressor — R407A compressor — 28.5 kW cooling, 10.06 kW input, COP 2.83 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZB66KCE-TF5 (R407A scroll, 60 Hz, MT)
RefrigerantR407A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool26.4 / 0.0 K
Cooling capacity @ 7.2/54.4 °C28.52 kW
Input power @ 7.2/54.4 °C10.06 kW
COP @ 7.2/54.4 °C2.83

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1015.843.684.31
-20 / 3013.125.482.39
-10 / 1024.133.706.52
-10 / 3020.145.903.41
-10 / 6013.4010.451.28
0 / 3029.876.024.96
0 / 6019.7811.021.79

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZB66KCE-TF5 (R134A scroll, 50 Hz, HT)R134a
compressorsCopeland ZB66KCE-TF5 (R404A scroll, 50 Hz, MT)R404A
compressorsCopeland ZB66KCE-TF5 (R404A scroll, 60 Hz, MT)R404A
compressorsCopeland ZB66KCE-TF5 (R407A scroll, 50 Hz, MT)R407A
compressorsCopeland ZB66KCE-TF5 (R407C scroll, 50 Hz, MT)R407C
compressorsCopeland ZB66KCE-TF5 (R407C scroll, 60 Hz, MT)R407C
compressorsCopeland ZB66KCE-TF5 (R407F scroll, 50 Hz, MT)R407F
compressorsCopeland ZB66KCE-TF5 (R407F scroll, 60 Hz, MT)R407F
compressorsCopeland ZB66KCE-TF5 (R448A scroll, 50 Hz, MT)R448A
compressorsCopeland ZB66KCE-TF5 (R448A scroll, 60 Hz, MT)R448A
compressorsCopeland ZB66KCE-TF5 (R449A scroll, 50 Hz, MT)R449A
compressorsCopeland ZB66KCE-TF5 (R449A scroll, 60 Hz, MT)R449A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy