Compressor — R404A compressor — 36.3 kW cooling, 15.94 kW input, COP 2.28 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZB95KCE-TED (R404A scroll, 60 Hz, MT) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 30.5 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 36.34 kW |
| Input power @ 7.2/54.4 °C | 15.94 kW |
| COP @ 7.2/54.4 °C | 2.28 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.5 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 27.35 | 6.18 | 4.43 |
| -20 / 30 | 22.27 | 9.24 | 2.41 |
| -10 / 10 | 40.41 | 6.75 | 5.98 |
| -10 / 30 | 32.97 | 9.60 | 3.43 |
| -10 / 60 | 18.37 | 18.01 | 1.02 |
| 0 / 30 | 47.03 | 10.08 | 4.66 |
| 0 / 60 | 27.01 | 18.08 | 1.49 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZB95KCE-TFD (R134A scroll, 50 Hz, HT) | R134a |
| compressors | Copeland ZB95KCE-TED (R134A scroll, 60 Hz, HT) | R134a |
| compressors | Copeland ZB95KCE-TED (R22 scroll, 50 Hz, HT) | R22 |
| compressors | Copeland ZB95KCE-TED (R22 scroll, 60 Hz, HT) | R22 |
| compressors | Copeland ZB95KCE-TFD (R404A scroll, 50 Hz, MT) | R404A |
| compressors | Copeland ZB95KCE-TFD (R507 scroll, 50 Hz, MT) | R507 |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.