Compressor — R407C compressor — 10.1 kW cooling, 3.49 kW input, COP 2.91 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZR40KTE-TFD (R407C scroll, 60 Hz, AC) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 10.14 kW |
| Input power @ 7.2/54.4 °C | 3.49 kW |
| COP @ 7.2/54.4 °C | 2.91 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 4.59 | 1.98 | 2.31 |
| -20 / 40 | 4.11 | 2.51 | 1.64 |
| -10 / 30 | 7.37 | 1.96 | 3.76 |
| -10 / 40 | 6.63 | 2.51 | 2.64 |
| 0 / 30 | 11.10 | 1.93 | 5.76 |
| 0 / 40 | 10.04 | 2.49 | 4.03 |
| 0 / 60 | 7.72 | 4.02 | 1.92 |
| 10 / 30 | 16.08 | 1.90 | 8.48 |
| 10 / 40 | 14.67 | 2.45 | 5.98 |
| 10 / 60 | 11.65 | 3.96 | 2.94 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZR40KTE-TFD (R407C scroll, 50 Hz, AC) | R407C |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.