Compressor — R407C compressor — 11.2 kW cooling, 3.95 kW input, COP 2.83 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZR44K5E-TFD (R407C scroll, 60 Hz, AC) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 11.18 kW |
| Input power @ 7.2/54.4 °C | 3.95 kW |
| COP @ 7.2/54.4 °C | 2.83 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 5.28 | 2.19 | 2.41 |
| -20 / 40 | 4.23 | 2.88 | 1.47 |
| -10 / 30 | 8.46 | 2.17 | 3.90 |
| -10 / 40 | 7.36 | 2.79 | 2.63 |
| 0 / 30 | 12.52 | 2.16 | 5.79 |
| 0 / 40 | 11.25 | 2.76 | 4.07 |
| 0 / 60 | 8.07 | 4.72 | 1.71 |
| 10 / 30 | 17.89 | 2.08 | 8.59 |
| 10 / 40 | 16.34 | 2.71 | 6.03 |
| 10 / 60 | 12.75 | 4.57 | 2.79 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZR44K5E-TFD (R407C scroll, 50 Hz, AC) | R407C |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.