Compressor — R407C compressor — 12.8 kW cooling, 4.60 kW input, COP 2.78 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZRD61KCE-TFD (R407C scroll, 50 Hz, AC) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 12.79 kW |
| Input power @ 7.2/54.4 °C | 4.60 kW |
| COP @ 7.2/54.4 °C | 2.78 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 5.62 | 2.36 | 2.38 |
| -20 / 40 | 5.11 | 2.83 | 1.81 |
| -10 / 30 | 8.90 | 2.55 | 3.49 |
| -10 / 40 | 8.30 | 3.10 | 2.68 |
| 0 / 30 | 13.75 | 2.69 | 5.11 |
| 0 / 40 | 12.57 | 3.30 | 3.81 |
| 0 / 60 | 9.90 | 4.93 | 2.01 |
| 10 / 30 | 20.92 | 2.88 | 7.25 |
| 10 / 40 | 18.65 | 3.51 | 5.32 |
| 10 / 60 | 14.84 | 5.27 | 2.82 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZRD61KCE-TFD (R407C scroll, 60 Hz, AC) | R407C |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.