Compressor — R407C compressor — 8.9 kW cooling, 3.19 kW input, COP 2.80 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZSH20KAE-TF5 (R407C scroll, 60 Hz, MT) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 18.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 8.92 kW |
| Input power @ 7.2/54.4 °C | 3.19 kW |
| COP @ 7.2/54.4 °C | 2.80 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 18.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 6.13 | 1.83 | 3.35 |
| -10 / 40 | 5.53 | 2.22 | 2.50 |
| 0 / 30 | 9.13 | 1.90 | 4.82 |
| 0 / 40 | 8.25 | 2.33 | 3.54 |
| 0 / 60 | 6.35 | 3.51 | 1.81 |
| 10 / 30 | 13.15 | 1.91 | 6.87 |
| 10 / 40 | 11.92 | 2.39 | 4.98 |
| 10 / 60 | 9.24 | 3.62 | 2.55 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZSH20KAE-TF5 (R134A scroll, 50 Hz, MT) | R134a |
| compressors | Copeland ZSH20KAE-TF5 (R134A scroll, 60 Hz, MT) | R134a |
| compressors | Copeland ZSH20KAE-TF5 (R22 scroll, 50 Hz, MT) | R22 |
| compressors | Copeland ZSH20KAE-TF5 (R22 scroll, 60 Hz, MT) | R22 |
| compressors | Copeland ZSH20KAE-TF5 (R407C scroll, 50 Hz, MT) | R407C |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.