Compressor — R407F compressor — 10.2 kW cooling, 3.62 kW input, COP 2.82 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZX29KCE-PFJ (R407F scroll, 50 Hz, MT) |
| Refrigerant | R407F |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 26.4 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 10.19 kW |
| Input power @ 7.2/54.4 °C | 3.62 kW |
| COP @ 7.2/54.4 °C | 2.82 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 4.71 | 1.99 | 2.36 |
| -20 / 40 | 4.09 | 2.56 | 1.60 |
| -10 / 30 | 7.28 | 2.00 | 3.63 |
| -10 / 40 | 6.41 | 2.57 | 2.50 |
| -10 / 60 | 4.48 | 4.25 | 1.06 |
| 0 / 30 | 10.80 | 2.02 | 5.34 |
| 0 / 40 | 9.57 | 2.57 | 3.72 |
| 0 / 60 | 6.83 | 4.22 | 1.62 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZX29KCE-PFJ (R134A scroll, 50 Hz, MT) | R134a |
| compressors | Copeland ZX29KCE-PFJ (R407A scroll, 50 Hz, MT) | R407A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.