Compressor — R404A compressor — 6.2 kW cooling, 3.15 kW input, COP 1.98 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YF13E5G-V100 (R404A low-temperature freezing scroll, 60 Hz, 380 V 3P) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 40.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 6.23 kW |
| Input power @ 7.2/54.4 °C | 3.15 kW |
| COP @ 7.2/54.4 °C | 1.98 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 40.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 30 | 1.70 | 1.24 | 1.38 |
| -40 / 40 | 1.52 | 1.56 | 0.98 |
| -30 / 30 | 2.57 | 1.33 | 1.93 |
| -30 / 40 | 2.32 | 1.63 | 1.43 |
| -20 / 30 | 3.67 | 1.44 | 2.55 |
| -20 / 40 | 3.31 | 1.73 | 1.92 |
| -20 / 60 | 2.48 | 2.68 | 0.93 |
| 0 / 30 | 6.90 | 1.70 | 4.06 |
| 0 / 40 | 6.18 | 2.05 | 3.01 |
| 0 / 60 | 4.61 | 3.25 | 1.42 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Invotech YF13E5G-Q100 (R404A low-temperature freezing scroll, 60 Hz, 380 V 3P) | R404A |
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.