Compressor — R404A compressor — 7.0 kW cooling, 3.38 kW input, COP 2.08 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YF20E2G-Q102 (R404A low-temperature freezing scroll, 50 Hz, 220 V 1P) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 38.3 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 7.02 kW |
| Input power @ 7.2/54.4 °C | 3.38 kW |
| COP @ 7.2/54.4 °C | 2.08 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 38.3 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 30 | 1.72 | 1.46 | 1.18 |
| -40 / 40 | 1.51 | 1.70 | 0.89 |
| -30 / 30 | 2.69 | 1.63 | 1.65 |
| -30 / 40 | 2.36 | 1.90 | 1.25 |
| -20 / 30 | 4.07 | 1.80 | 2.25 |
| -20 / 40 | 3.58 | 2.10 | 1.70 |
| -20 / 60 | 2.44 | 3.05 | 0.80 |
| 0 / 30 | 8.25 | 2.20 | 3.74 |
| 0 / 40 | 7.26 | 2.55 | 2.85 |
| 0 / 60 | 4.93 | 3.54 | 1.39 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.