Compressor — R449A compressor — 9.9 kW cooling, 3.84 kW input, COP 2.58 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YF25E1G-Q100 (R449A low-temperature freezing scroll, 50 Hz, 380 V 3P) |
| Refrigerant | R449A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 40.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 9.91 kW |
| Input power @ 7.2/54.4 °C | 3.84 kW |
| COP @ 7.2/54.4 °C | 2.58 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 40.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 30 | 1.95 | 1.57 | 1.24 |
| -40 / 40 | 1.73 | 1.98 | 0.88 |
| -30 / 30 | 3.06 | 1.87 | 1.64 |
| -30 / 40 | 2.79 | 2.31 | 1.21 |
| -20 / 30 | 4.69 | 2.04 | 2.30 |
| -20 / 40 | 4.27 | 2.50 | 1.71 |
| -20 / 60 | 3.23 | 4.03 | 0.80 |
| 0 / 30 | 10.29 | 2.31 | 4.44 |
| 0 / 40 | 9.26 | 2.76 | 3.35 |
| 0 / 60 | 6.98 | 4.23 | 1.65 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.