Compressor — R449A compressor — 11.9 kW cooling, 4.60 kW input, COP 2.59 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YF25E7G-Q100 (R449A low-temperature freezing scroll, 60 Hz, 220 V 3P) |
| Refrigerant | R449A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 40.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 11.89 kW |
| Input power @ 7.2/54.4 °C | 4.60 kW |
| COP @ 7.2/54.4 °C | 2.59 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 40.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 30 | 2.34 | 1.88 | 1.24 |
| -40 / 40 | 2.08 | 2.37 | 0.88 |
| -30 / 30 | 3.68 | 2.24 | 1.64 |
| -30 / 40 | 3.35 | 2.77 | 1.21 |
| -20 / 30 | 5.63 | 2.44 | 2.31 |
| -20 / 40 | 5.12 | 2.99 | 1.71 |
| -20 / 60 | 3.88 | 4.82 | 0.80 |
| 0 / 30 | 12.35 | 2.77 | 4.45 |
| 0 / 40 | 11.11 | 3.31 | 3.36 |
| 0 / 60 | 8.37 | 5.06 | 1.65 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |