Compressor — R404A compressor — 12.8 kW cooling, 5.51 kW input, COP 2.32 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YF29E1G-Q100 (R404A low-temperature freezing scroll, 60 Hz, 460 V 3P) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 38.3 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 12.78 kW |
| Input power @ 7.2/54.4 °C | 5.51 kW |
| COP @ 7.2/54.4 °C | 2.32 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 38.3 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 30 | 3.14 | 2.28 | 1.38 |
| -40 / 40 | 2.75 | 2.70 | 1.02 |
| -30 / 30 | 4.90 | 2.56 | 1.91 |
| -30 / 40 | 4.31 | 3.02 | 1.43 |
| -20 / 30 | 7.41 | 2.86 | 2.59 |
| -20 / 40 | 6.51 | 3.36 | 1.94 |
| -20 / 60 | 4.45 | 4.96 | 0.90 |
| 0 / 30 | 15.02 | 3.53 | 4.25 |
| 0 / 40 | 13.22 | 4.11 | 3.21 |
| 0 / 60 | 8.97 | 5.79 | 1.55 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |