Compressor — R404A compressor — 6.7 kW cooling, 2.80 kW input, COP 2.38 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YM43E6G-100 (R404A medium-temperature refrigeration scroll, 50 Hz, 220 V 3P) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 28.3 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 6.67 kW |
| Input power @ 7.2/54.4 °C | 2.80 kW |
| COP @ 7.2/54.4 °C | 2.38 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 28.3 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 10 | 3.08 | 0.97 | 3.19 |
| -30 / 30 | 2.41 | 1.34 | 1.81 |
| -20 / 10 | 4.58 | 1.06 | 4.32 |
| -20 / 30 | 3.66 | 1.48 | 2.48 |
| -10 / 10 | 6.77 | 1.19 | 5.71 |
| -10 / 30 | 5.39 | 1.63 | 3.31 |
| -10 / 60 | 3.23 | 2.74 | 1.18 |
| 10 / 30 | 10.91 | 1.92 | 5.67 |
| 10 / 60 | 6.40 | 3.12 | 2.05 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.