Compressor — R404A compressor — 9.2 kW cooling, 3.52 kW input, COP 2.60 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YM49E1G-100 (R404A medium-temperature refrigeration scroll, 60 Hz, 460 V 3P) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 14.4 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 9.15 kW |
| Input power @ 7.2/54.4 °C | 3.52 kW |
| COP @ 7.2/54.4 °C | 2.60 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 14.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 10 | 4.05 | 1.29 | 3.14 |
| -30 / 30 | 3.10 | 1.85 | 1.68 |
| -20 / 10 | 5.95 | 1.39 | 4.29 |
| -20 / 30 | 4.94 | 1.98 | 2.49 |
| -20 / 60 | 2.42 | 3.25 | 0.75 |
| -10 / 10 | 8.57 | 1.55 | 5.53 |
| -10 / 30 | 7.44 | 2.13 | 3.50 |
| -10 / 60 | 4.02 | 3.53 | 1.14 |
| 10 / 30 | 14.27 | 2.47 | 5.76 |
| 10 / 60 | 8.74 | 3.91 | 2.23 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |