Invotech YM60E5G-100 (R404A medium-temperature refrigeration scroll, 60 Hz, 380 V 3P)
Compressor — R404A compressor — 11.1 kW cooling, 4.58 kW input, COP 2.44 at the AHRI 7.2/54.4 °C rating point.
An Invotech listing, from the manufacturer's published data.
Units: SI · US customary
Published specification
| Model | Invotech YM60E5G-100 (R404A medium-temperature refrigeration scroll, 60 Hz, 380 V 3P) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 28.3 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 11.15 kW |
| Input power @ 7.2/54.4 °C | 4.58 kW |
| COP @ 7.2/54.4 °C | 2.44 |
The map across its envelope
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 28.3 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| 7.2 / 54.4 | 11.15 | 4.58 | 2.44 |
| -20 / 40 | 5.42 | 2.87 | 1.89 |
| -10 / 40 | 7.93 | 3.16 | 2.51 |
| 0 / 40 | 11.32 | 3.42 | 3.30 |
The rating point and three conditions across the published envelope. The whole map — every condition, the envelope and the curves — is in the builder: open this machine in the app. It solves any point inside the envelope, and warns past it.
Open this compressor in the app — the compressor-map tab, with its rating at any condition, its envelope, capacity and power lines and curves plotted, and the refrigerant's pressure–temperature chart a click away; or open the builder and pick it from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
How the model reads against this maker's data
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.