Compressor — R454C compressor — 9.2 kW cooling, 3.02 kW input, COP 3.06 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YM60U1G-100 (R454C medium-temperature refrigeration scroll, 50 Hz, 380 V 3P) |
| Refrigerant | R454C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 30.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 9.22 kW |
| Input power @ 7.2/54.4 °C | 3.02 kW |
| COP @ 7.2/54.4 °C | 3.06 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 10 | 3.29 | 1.19 | 2.76 |
| -30 / 30 | 2.60 | 1.61 | 1.62 |
| -20 / 10 | 5.24 | 1.29 | 4.07 |
| -20 / 30 | 4.22 | 1.75 | 2.41 |
| -10 / 10 | 7.96 | 1.43 | 5.56 |
| -10 / 30 | 6.34 | 1.86 | 3.40 |
| 10 / 30 | 13.40 | 2.14 | 6.26 |
| 10 / 60 | 9.34 | 3.36 | 2.78 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Invotech YM60U1G-100 (R455A medium-temperature refrigeration scroll, 50 Hz, 380 V 3P) | R455A |
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.