Compressor — R404A compressor — 36.4 kW cooling, 14.46 kW input, COP 2.52 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YSM235E1G-100 (R404A medium-temperature refrigeration scroll, 50 Hz, 380 V 3P) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 28.3 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 36.45 kW |
| Input power @ 7.2/54.4 °C | 14.46 kW |
| COP @ 7.2/54.4 °C | 2.52 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 28.3 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 10 | 16.86 | 4.99 | 3.38 |
| -30 / 30 | 13.18 | 6.90 | 1.91 |
| -20 / 10 | 25.03 | 5.48 | 4.57 |
| -20 / 30 | 20.00 | 7.63 | 2.62 |
| -10 / 10 | 37.02 | 6.13 | 6.04 |
| -10 / 30 | 29.46 | 8.41 | 3.50 |
| -10 / 60 | 17.65 | 14.17 | 1.25 |
| 10 / 30 | 59.62 | 9.94 | 6.00 |
| 10 / 60 | 34.96 | 16.14 | 2.17 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Invotech YSM235E1G-100 (R404A medium-temperature refrigeration scroll, 60 Hz, 460 V 3P) | R404A |
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.