Compressor — R407C compressor — 31.1 kW cooling, 10.14 kW input, COP 3.07 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YW245T1-100 (R407C heat-pump water heater scroll, 60 Hz, 460 V 3P) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 31.14 kW |
| Input power @ 7.2/54.4 °C | 10.14 kW |
| COP @ 7.2/54.4 °C | 3.07 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 20 | 15.05 | 4.59 | 3.28 |
| -20 / 40 | 12.43 | 6.42 | 1.93 |
| -10 / 20 | 22.77 | 5.07 | 4.49 |
| -10 / 40 | 18.99 | 7.10 | 2.67 |
| 0 / 20 | 32.81 | 5.83 | 5.63 |
| 0 / 40 | 27.86 | 7.59 | 3.67 |
| 0 / 70 | 19.12 | 12.93 | 1.48 |
| 10 / 40 | 39.25 | 8.29 | 4.74 |
| 10 / 70 | 27.95 | 13.72 | 2.04 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Invotech YW245T1-100 (R407C heat-pump water heater scroll, 50 Hz, 380 V 3P) | R407C |
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.