Compressor — R404A compressor — 21.1 kW cooling, 8.26 kW input, COP 2.56 at the AHRI 7.2/54.4 °C rating point.
A Tecumseh listing, from the manufacturer's published data.
| Model | Tecumseh AG2522Z-TZ1A (R404A hermetic, LBP, Tecumseh Europe, 50 Hz) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 57.2 / 7.8 K |
| Cooling capacity @ 7.2/54.4 °C | 21.12 kW |
| Input power @ 7.2/54.4 °C | 8.26 kW |
| COP @ 7.2/54.4 °C | 2.56 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 57.2 K superheat and 7.8 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -40 to -10 °C, condensing 30 to 60 °C (a rectangle).
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 30 | 3.53 | 2.99 | 1.18 |
| -40 / 40 | 2.93 | 2.42 | 1.21 |
| -40 / 60 | 0.96 | 1.31 | 0.73 |
| -30 / 30 | 5.29 | 3.33 | 1.59 |
| -30 / 40 | 4.75 | 3.08 | 1.54 |
| -30 / 60 | 3.04 | 2.62 | 1.16 |
| -20 / 30 | 8.62 | 3.89 | 2.22 |
| -20 / 40 | 7.97 | 3.94 | 2.02 |
| -20 / 60 | 6.19 | 4.06 | 1.52 |
| -10 / 30 | 13.51 | 4.68 | 2.89 |
| -10 / 40 | 12.58 | 4.99 | 2.52 |
| -10 / 60 | 10.40 | 5.64 | 1.85 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Tecumseh hermetic compressor maps, the maker's own coefficient sets | 864 maps from 297 models (R404A 324, R134a 178, R290 109, R22 97, R513A 89, R1234yf 53, R600a 10, R410A 4) at 93 application × refrigerant × frequency listings | power reads the selector's point within 0.95 % on every map (units and coefficient order, BTU/h sets scaled and Fahrenheit sets substituted exactly); 522 maps rate at their own basis and read the selector's capacity within 1 %; on the 342 the selector corrected from a liquid-temperature or return-gas basis to the regime, this solver's AHRI 540 §6 correction reproduces the selector's corrected capacity within +0.3 % on average (the raw polynomial sits +9.5 % over it), single maps ±11 % where a return-gas basis is carried as one reference superheat. 2 028 zeotrope rows (R448A, R449A, R452A, R454C, R455A, R407C) are withheld: Tecumseh publishes them on the glide's mid-point where AHRI 540 and this catalog rate on dew points |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.