Companies

Soler & Palau Unclaimed

41 listings in HVAC Builder's catalog from Soler & Palau's published data, selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; Soler & Palau has not claimed it.

Are you Soler & Palau?

Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. We confirm each claim by hand before it takes effect; from then the page and its listings are yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page

Components

Showing 25–41 of 41

NameTypeRatingMarketsOpen in the builder
Soler & Palau SDB size 36 belt-drive downblast roof exhauster (650 rpm, 5 HP) CatalogFansFan rated 6.24 m³/s at 4.46 kW.NAOpen in the builder
Soler & Palau STXB size 22 high-pressure belt-drive upblast roof exhauster (1350 rpm, 3 HP) CatalogFansFan rated 3.01 m³/s at 2.92 kW.NAOpen in the builder
Soler & Palau SDB size 42 belt-drive downblast roof exhauster (575 rpm, 7-1/2 HP) CatalogFansFan rated 8.36 m³/s at 6.24 kW.NAOpen in the builder
Soler & Palau STXB size 24 belt-drive upblast roof exhauster (900 rpm, 2 HP) CatalogFansFan rated 2.89 m³/s at 1.84 kW.NAOpen in the builder
Soler & Palau SDB size 8 belt-drive downblast roof exhauster (2100 rpm, 1/3 HP) CatalogFansFan rated 0.34 m³/s at 0.34 kW.NAOpen in the builder
Soler & Palau STXB size 24 high-pressure belt-drive upblast roof exhauster (1150 rpm, 3 HP) CatalogFansFan rated 2.52 m³/s at 2.57 kW.NAOpen in the builder
Soler & Palau STXB size 27 belt-drive upblast roof exhauster (750 rpm, 2 HP) CatalogFansFan rated 3.64 m³/s at 1.96 kW.NAOpen in the builder
Soler & Palau STXB size 27 high-pressure belt-drive upblast roof exhauster (950 rpm, 3 HP) CatalogFansFan rated 4.41 m³/s at 2.70 kW.NAOpen in the builder
Soler & Palau STXB size 30 belt-drive upblast roof exhauster (1000 rpm, 7-1/2 HP) CatalogFansFan rated 6.11 m³/s at 6.54 kW.NAOpen in the builder
Soler & Palau STXB size 30 high-pressure belt-drive upblast roof exhauster (1150 rpm, 7-1/2 HP) CatalogFansFan rated 5.64 m³/s at 6.91 kW.NAOpen in the builder
Soler & Palau STXB size 33 belt-drive upblast roof exhauster (850 rpm, 7-1/2 HP) CatalogFansFan rated 6.47 m³/s at 6.01 kW.NAOpen in the builder
Soler & Palau STXB size 33 high-pressure belt-drive upblast roof exhauster (1000 rpm, 7-1/2 HP) CatalogFansFan rated 5.68 m³/s at 6.58 kW.NAOpen in the builder
Soler & Palau STXB size 36 belt-drive upblast roof exhauster (750 rpm, 7-1/2 HP) CatalogFansFan rated 8.00 m³/s at 6.83 kW.NAOpen in the builder
Soler & Palau STXB size 36 high-pressure belt-drive upblast roof exhauster (950 rpm, 10 HP) CatalogFansFan rated 6.19 m³/s at 9.34 kW.NAOpen in the builder
Soler & Palau STXB size 42 belt-drive upblast roof exhauster (600 rpm, 7-1/2 HP) CatalogFansFan rated 8.98 m³/s at 6.97 kW.NAOpen in the builder
Soler & Palau STXB size 48 belt-drive upblast roof exhauster (525 rpm, 10 HP) CatalogFansFan rated 9.82 m³/s at 8.44 kW.NAOpen in the builder
Soler & Palau STXB size 8 belt-drive upblast roof exhauster (2100 rpm, 1/3 HP) CatalogFansFan rated 0.33 m³/s at 0.34 kW.NAOpen in the builder
‹ Previous12

How the model reads against Soler & Palau's data

Fan power through the fan laws, one curve per fan from a US multi-rating table3 382 cells over 41 fans; 69 withheld by nameevery held cell's BHP within a band of 2 % plus the half-hundredth it is printed to (0.005 BHP, part of the band: the worst cell sits at 0.999 of it, and four held cells from 0.5 BHP read past a bare 2 % — SDB-33 at 650 rpm and 1.25 in., SDB-36 at 425 rpm and 0.625 in., STXB-33 at 400 rpm and 0.375 in. and STXB-36 at 600 rpm and 1.25 in., 2.05–2.2 % off), and its speed within 0.87 %, read back by the solver's own fan-law solve; RMS 0.43 % on power over the 2 396 cells from 0.5 BHP up. Each withheld cell is its row's last or followed only by withheld cells: 19 print more air at a higher static than the cell before them, the rest sit on the stall side of their speed's curve. SDB-48 is not listed — 18 of its 73 cells would need naming, six inside their rows

From the validation page; every row is held by a test.

Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.