8 listing(s) in HVAC Builder's catalog from Wieland's published data, selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; Wieland has not claimed it.

Are you Wieland?

Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. We confirm each claim by hand before it takes effect; from then the page and its listings are yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page

Listings

All kindsPipe-in-pipe exchanger 8
All marketsEU 8
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1–8 of 8

Wieland WKC 10 coaxial condenser (9.6 kW at 1.0 m³/h of 30 °C water, 45 °C condensing, R410A)

Coaxial condenser — 9.6 kW into water 30.0 to 38.3 °C, condensing at 45.0 °C, 0.28 kg/s.

catalog
Pipe-in-pipe exchanger · EU

Wieland WKC 15 coaxial condenser (21.0 kW at 1.6 m³/h of 30 °C water, 45 °C condensing, R410A)

Coaxial condenser — 21.0 kW into water 30.0 to 41.3 °C, condensing at 45.0 °C, 0.44 kg/s.

catalog
Pipe-in-pipe exchanger · EU

Wieland WKC 20 coaxial condenser (32.7 kW at 2.7 m³/h of 30 °C water, 45 °C condensing, R410A)

Coaxial condenser — 32.7 kW into water 30.0 to 40.4 °C, condensing at 45.0 °C, 0.75 kg/s.

catalog
Pipe-in-pipe exchanger · EU

Wieland WKC 45 coaxial condenser (70.0 kW at 5.4 m³/h of 30 °C water, 45 °C condensing, R410A)

Coaxial condenser — 70.0 kW into water 30.0 to 41.2 °C, condensing at 45.0 °C, 1.50 kg/s.

catalog
Pipe-in-pipe exchanger · EU

Wieland WKE 10 coaxial evaporator (10.2 kW at 1.6 m³/h of 12 °C water, 0 °C evaporating, R410A)

Coaxial evaporator — 10.2 kW from water 12.0 to 6.5 °C, evaporating at 0.0 °C, 0.44 kg/s.

catalog
Pipe-in-pipe exchanger · EU

Wieland WKE 16 coaxial evaporator (14.7 kW at 2.5 m³/h of 12 °C water, 0 °C evaporating, R410A)

Coaxial evaporator — 14.7 kW from water 12.0 to 6.9 °C, evaporating at 0.0 °C, 0.69 kg/s.

catalog
Pipe-in-pipe exchanger · EU

Wieland WKE 24 coaxial evaporator (17.7 kW at 3.0 m³/h of 12 °C water, 0 °C evaporating, R410A)

Coaxial evaporator — 17.7 kW from water 12.0 to 6.9 °C, evaporating at 0.0 °C, 0.83 kg/s.

catalog
Pipe-in-pipe exchanger · EU

Wieland WKE 44 coaxial evaporator (41.9 kW at 7.0 m³/h of 12 °C water, 0 °C evaporating, R410A)

Coaxial evaporator — 41.9 kW from water 12.0 to 6.9 °C, evaporating at 0.0 °C, 1.94 kg/s.

catalog
Pipe-in-pipe exchanger · EU

How the model reads against Wieland's data

Coaxial exchanger model against a maker's measured condenser and evaporator tables, one conductance per model554 over 8 modelsevery rating reproduced exactly. Condensers on R410A (R404A/R507 is printed identical): −13 to +16 % of the printed duty, RMS 7.9 %, the condensing temperature within 3.0 K — at one flow the duty is proportional to the temperature difference as the model has it, but the conductance rises with flow (as flow^0.4 on three of the four) and at the lowest flows the hot gas heats the water past the condensing temperature, which no isothermal model does. Evaporators on R410A: −18 to +63 %, RMS 22 %, within 3.2 K — the conductance rises with flow (flow^0.3–0.5) and with the temperature difference (as boiling that strengthens with the heat flux, and a 5 K suction superheat that takes more of the tube the smaller the difference, would make it), so one conductance over-reads most at a low flow and a 6 K difference. The other refrigerants are R410A times one ratio each — R134a 12 % under on the condensers and 20 % under on the evaporators, R404A/R507 7 % over on the evaporators — which a listing that carries no refrigerant reads as R410A

From the validation page; every row is held by a test.

Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.