Worked cases · Singapore
Two data halls on a chilled-water CRAH fed by a chiller holding 13 °C, a UPS room on a remote condensing unit and an indoor DX unit, and a staffed NOC on a split — held on Singapore's year.
Open the building in the Simulate tabNorthgate is two data halls with 42 and 28 kW of IT around the clock on a computer-room air handler — a deep coil and a draw-through plug fan, no outside air, the halls' return on the coil — fed by the modular chiller holding 13 °C: a warm loop of the kind TC 9.9's A1 band permits. A UPS room sits on a remote condensing unit and an indoor DX unit cut along the refrigerant lines, and a NOC on the split.
Two things the first run taught: a 90 kW-class chiller ran flat out against 50 + 35 kW of IT, and a well-mixed hall at 25 °C on 14 °C water limits the CRAH to an 18 °C supply — 73 kW against 75 — so the halls hold 26 °C (A1 allows 27) on a 13 °C loop. In winter the indoor unit's economiser holds the UPS room on outside air while the condensing unit idles.
On Singapore's year the building reads 1 003 MWh of cooling on 330 MWh of electricity, the halls held at 26 °C to within five hours after the cold-start hour.
| Cooling / electricity | 1 003 MWh / 330 MWh |
| Halls | 26 °C to within 5 hours a year |
| Loop | 13 °C leaving water — an A1-band warm loop |
Readings of the shipped model on the building's own PVGIS typical meteorological year; engineering estimates from catalog data and published correlations. The building runs on every plan, including Free, a few times a day.